Double-break Disconnectors

Type SSBIII up to 550 kV
The horizontal double-break disconnectors consist of three poles. Each pole has a frame, two supporting insulators at each end and one rotating insulator in the center, on which the main blade is mounted.

• More than 75 years of experience
• Durable and reliable design
• Over 120,000 disconnectors and earthing switches are in service in more than 100 countries throughout the world
• Virtually maintenance-free
Frame
The frame is made of a square tube in which in the center the bearing housing and the turntable are installed. The turntable is supported by two roller bearings. The bearing housing is sealed and filled up with grease, to ensure a long lifetime. All steel parts of the disconnector are hot-dip galvanized.
Insulators
The disconnectors can be equipped with insulators in accordance with IEC, ANSI, or DIN specifications.
Drive Mechanism
The disconnectors and/or earthing switches can be single-pole or three-pole operated by means of a motor-operated drive mechanism or a manual-operated drive mechanism. In case only one drive mechanism is used for three-pole operation, the poles are interconnected by means of adjustable coupling rods. The drive mechanism also houses the auxiliary contacts for position indication.
Main Blade
The main blade consists of two fixed contacts, mounted on the supporting insulators, and a moving blade mounted on the rotating insulator. The main contacts are installed inside the main blade. They are made of copper, with a silver-plated surface.
Each contact finger is provided with stainless steel springs to ensure reliable contact pressure. The contacts are self-cleansing, which makes the disconnector suitable for installation in areas with severe climatic conditions. Depending on the voltage rating, anti-corona shields will be provided.
Earthing switch
HAPAM disconnectors may be equipped with earthing switches, which can be built on to the right hand side and/or to the left hand side. The earthing switch consists of an aluminum tube, provided with silver-plated contacts at both ends.
Testing
The disconnectors and earthing switches are designed and tested in accordance with the latest IEC specifications. HAPAM maintains a quality assurance system according to ISO 9001, certified by KEMA.
Installation
The disconnectors and earthing switches are pre-assembled and adjusted in our works as completely as possible.
The construction is designed so that all disconnectors can be installed and adjusted at the site very easily, without the need of any special tools. HAPAM provides clear installation instructions and assembly drawings.
Maintenance
The disconnectors and earthing switches supplied by HAPAM are designed to ensure that they are virtually maintenance-free. However, to warrant a long and trouble-free service period, we advise that a visual inspection of the contacts and bearing points be carried out at regular intervals.
Rated VoltagekV72.5123145245550
Lightning Impulse Withstand Voltage
to earthkV32555065010501550
across the isolating distancekV37563075012001550
+ 315
Power Frequency Withstand Voltage
to earthkV140230275460620
across the isolating distancekV160265315530800
Lightning Impulse Withstand Voltage
to earthkV1175
across the isolating distancekV900
+ 450
Current and Short Circuit Ratings
1600 A-80 kA peak – 32 kA/3 sec
2000 A-100 kA peak – 40 kA/3 sec
3150 A-125 kA peak – 50 kA/3 sec
4000 A-160 kA peak-63 kA/3 sec