smartCOUNT
Surge Arrester Monitoring System

smartCOUNT is an intelligent surge arrester monitoring system. It measures leakage current as well as impulse currents automatically and can deliver online accessible measuring values and trend curves.
smartCOUNT reduces planned and unplanned shutdowns by detecting faulty arresters and gives reliable information about their status. It can be installed to all gapless ZnO surge arresters and in that way improves reliability of new and existing substations. Constantly listening to special requests and requirements of every customer around the world, Tridelta Meidensha team developed another ground-breaking solution for trustworthy security. smartCOUNT is the first one of a new generation of condition monitors, detecting and even distinguishing typical failures in time.
smartCOUNT reduces planned and unplanned shutdowns by detecting faulty arresters and gives reliable information about their status. It can be installed to all gapless ZnO surge arresters and in that way improves reliability of new and existing substations. Constantly listening to special requests and requirements of every customer around the world, Tridelta Meidensha team developed another ground-breaking solution for trustworthy security. smartCOUNT is the first one of a new generation of condition monitors, detecting and even distinguishing typical failures in time.
Easy installation to any gapless MO surge arrester
Maintenance-free for lifetime
IP67 approved, UV, temperature and weather resistant
Self-sufficient power supply from leakage current energy
Easy data collection with smartphone via NFC
Access monitoring data online or download as excel
Automatic error compensation (acc. IEC 60099-5 Method B2)
Proper calculation of the resistive current component
High resolution of leakage current records down to 1 µA
Impulse counting and amplitude measurement up to 100kA
E-Mail alert for critical surge arrester condition
Free expert support channel
| Measuring Range | |
|---|---|
| total leakage current | 0 μA to 50 mA peak/√2 |
| 3rd Harmonic Leakage Current | 0 μA to 5 mA r.m.s |
| Resistive Leakage Current | 0μA to 5 mA r.m.s |
| Leakage Current Resolution | 1μA |
| Frequency | 60 Hz |
| Measurement cycle | 1/hour, 1/day, 1/week |
| Surge counting classification (8/20?s) | x ≤ 100 A 100 A < x ≤ 1000 A 1000 A < x ≤ 5000 A 5000 A < x ≤ 1000 A 10000 A < x ≤ 40000 A 40000 A < x ≤ 100000 A |
| Memory (cyclic buffer) | 1000 leakage current entries 1000 impulse current entries |
| Time stamp format | YYYY-MM-DD hh:mm:ss |
| Operating temperature | -40 to +60 C |
| Data cable length | 1 to 30 m |