HV Surge Arrester Silicone / HS Silikon SBKC

Metal oxide surge arrester with polymer cage-design Type series SBKC 3 to 144/SL-0
Tansformers, switch-gears and plants against atmospheric and switching overvoltages

Selection of metal oxide surge arresters
The selection of the rated and the continuous operating voltage of the arresters is depending on the neutral performance of the networks. Guidelines for selection: see VDE 0675-5 and IEC 60099-5

Design
Type tested according to IEC 60099-4 active part reinforced with FRP rods; directly molded with silicon color: grey, RAL 7040 fittings: Al alloy connections: clamps, screws, nuts stainless steel

Optional accessories
surge counter, monitoring spark gap, smartCOUNT Technical Parameters acc. to IEC 60099-4 Rated voltage Ur : 4 to 144 kV Arrester class: station SL Nominal discharge current: 10 kA Switching impulse discharge current: 0,5 kA Repetitive charge transfer rating Qrs: 1,2 C Thermal energy rating Wth: 4,5 kJ/kVUr Line discharge class: 2 High current impulse (4/10µs): 100 kA Rated short circuit current: 40 kA Operating conditions Ambient temperature: -60 °C to +60 °C Rated frequency: 48 Hz to 62 Hz
Field of application
Protection of transformers, switch-gears and plants against atmospheric and switching overvoltages
Selection of metal oxide (Zn0) surge arresters
The selection of the rated and the continuous operating voltage of the arresters depends on the neutral point treatment of the network. Guidelines for selection: see VDE 0675- 5 and IEC 60099-5
Design
Type tested according to IEC 60099-4 active part reinforced with FRP rods; directly molded with silicon
Colour: Grey RAL 7040
Fittings: Al alloy
Connections: clamps, screws, nuts stainless steel
Optional accessories
Monitoring spark gap, surge counter, diagnostic appliance
ProductSBKC size 0SBKC size II
High System Voltage UskV170420 *
Max. Rated Voltage UrkV144360 *
max. Nominal Discharge Current ln
(at 8/20μs waveshape)
kA1010
max. Thermal Energy Absorption CapabilitykJ per kV of Ur4.59.2
Max. Line Discharge Class24
Qrs (accor. IEC 60099-4 Edt. 3.0)1.22.8
High Current Withstand Strength 4/10 μskA100100
Max. Low Current Withstand Strength 2msA5001500
Max. Short Circuit / Pressure Relief CapabilitykA – 0.2s4063
Mechanical Strength: Specific short-term load SSLNm1,2004,000

*Higher rating for line arrester applications (TLA) available on request